p2293 Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.00 [s]
Max:
100.00 [s]
Factory setting:
1.00 [s]
Description: Sets the ramping time for the output signal of the technology controller.
Dependency: See also: p2291, p2292
Note
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294 CO: Technology controller output signal / Tec_ctrl outp_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the output signal of the technology controller.
Dependency: See also: p2295
p2295 CO: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
-100.00 [%]
Max:
100.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling for the output signal of the technology controller.
p2296[0...n] CI: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
2295[0]
Description: Sets the signal source for the scaling value of the technology controller.
Dependency: See also: p2295
p2297[0...n] CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
1084[0]
Description: Sets the signal source for the maximum limiting of the technology controller.
Dependency: See also: p2291
Parameters
7.3 Parameters
SINAMICS G120XA converter
618 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB