p11071 Free tec_ctrl 0 actual value inversion / Ftec0 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0
Max:
1
Factory setting:
0
Description: Sets the inversion of the actual value signal of the free technology controller 0.
Value: 0: No inversion
1: Inversion
r11072 CO: Free tec_ctrl 0 actual value after limiter / Ftec0 act v af lim
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_2 Unit selection: p11026 Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the actual value after the limiter of the free technology controller 0.
r11073 CO: Free tec_ctrl 0 system deviation / Ftec0 sys dev
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_2 Unit selection: p11026 Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the system deviation of the free technology controller 0.
p11074 Free tec_ctrl 0 differentiation time constant / Ftec0 D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
0.000 [s]
Description: Sets the time constant for the differentiation (D component) of the free technology controller 0.
Note
Value = 0: Differentiation is deactivated.
p11080 Free tec_ctrl 0 proportional gain / Ftec0 Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.000
Max:
1000.000
Factory setting:
1.000
Description: Sets the proportional gain (P component) of the free technology controller 0.
Note
Value = 0: The proportional gain is deactivated.