Locked functions:
Automatic controller optimization
Stationary or rotating measurement of the motor data identification
Deleting the alarm history and the fault history
Generating acceptance documents for safety functions
Executable functions:
Restoring factory settings
Acknowledging faults
Displaying faults, alarms, fault history, and alarm history
Reading out the diagnostic buffer
Uploading adjustable parameters that can be changed or read when know-how
protection is active.
When know-how protection is active, support can only be provided (from Technical Support)
after prior agreement from the machine manufacturer (OEM).
Know-how protection without copy protection
You can transfer converter settings to other converters using a memory card or an Operator
Panel.
Know-how protection with basic copy protection
After replacing a converter, to be able to operate the new converter with the settings of the
replaced converter without knowing the password, the memory card must be inserted in the
new converter.
Know-how protection with extended copy protection
It is not possible to insert and use the memory card in another converter without knowing the
password.
Commissioning know-how protection
1. Check as to whether you must extend the exception list.
List of exceptions (Page 741)
2. Activate the know-how protection.
Know-how protection (Page 741)
Parameters
Table 8-3 Parameters that can be changed with active know-how protection
Number Name
p0003 Access level / Acc_level
p0010 Drive commissioning parameter filter / Drv comm par_filt
p0124[0...n] CU detection using LED / CU detect LED
p0970 Reset drive parameters / Drive par reset
Saving the settings and series commissioning
8.6 Know-how protection
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 739