Siemens SINAMICS G120XA - CO: Accelerating Torque; M_Accel; CO: Torque Setpoint before Supplementary Torque; M_Set Bef. M_Suppl

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WARNING
The acceleration precontrol r1518 is kept at the old value if the ramp-function generator tracking (r1199.5) is active or
the ramp-function generator output is set (r1199.3). This is used to avoid torque peaks. Depending on the application,
it may therefore be necessary to disable the ramp-function generator tracking (p1145 = 0) or the acceleration
precontrol (p1496 = 0).
The acceleration precontrol is set to zero, if the Vdc control is active (r0056.14/15).
Note
The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration precontrol may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint) and
the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the precontrol mode is not used if there is gearbox backlash.
p1496[0...n] Acceleration precontrol scaling / a_prectrl scal
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6020, 6031
Min:
0.0 [%]
Max:
10000.0 [%]
Factory setting:
100.0 [%]
Description: Sets the scaling for the acceleration precontrol of the speed/velocity controller.
Dependency: See also: p0341, p0342
WARNING
The acceleration precontrol r1518 is kept at the old value if the ramp-function generator tracking (r1199.5) is active or
the ramp-function generator output is set (r1199.3). This is used to avoid torque peaks. Depending on the application,
it may therefore be necessary to disable the ramp-function generator tracking (p1145 = 0) or the acceleration
precontrol (p1496 = 0).
The acceleration precontrol is set to zero, if the Vdc control is active (r0056.14/15).
Note
The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration precontrol may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint) and
the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the precontrol mode is not used if there is gearbox backlash.
r1508 CO: Torque setpoint before supplementary torque / M_set bef. M_suppl
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dynamic index: -
Unit group: 7_1 Unit selection: p0505 Function diagram: 6030, 6060,
6722
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description: Displays the torque setpoint before entering the supplementary torque.
For closed-loop speed control, r1508 corresponds to the speed controller output.
r1518[0...1] CO: Accelerating torque / M_accel
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dynamic index: -
Unit group: 7_1 Unit selection: p0505 Function diagram: 6060
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description: Displays the accelerating torque for precontrol of the speed controller.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 523