EasyManua.ls Logo

Siemens SINAMICS G120XA - Alarm History; Shifting Removed Alarms into the Alarm History; Parameters of the Alarm Buffer and the Alarm History

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In the alarm buffer, the alarms are sorted according to "Alarm time received". If the alarm buffer
is completely filled and an additional alarm occurs, then the converter overwrites the values
with Index [7].
Alarm history
$ODUPEXIIHU
,QFRPLQJDODUPZKHQDODUPEXIIHULV
FRPSOHWHO\IXOO
$ODUPKLVWRU\
5HPRYHGDODUP
2OG
1HZ
1HZ
2OG
$ODUPWLPHUHFHLYHG
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
Figure 9-2 Shifting removed alarms into the alarm history
If the alarm buffer is completely filled and an additional alarm occurs, the converter shifts all
removed alarms into the alarm history. The following occurs in detail:
1. To create space after position [8] in the alarm history, the converter shifts the alarms already
stored in the alarm history "down" by one or more positions.
If the alarm history is completely full, the converter will delete the oldest alarms.
2. The converter moves the removed alarms from the alarm buffer to the now freed up
positions of the alarm history.
Alarms that have not been removed remain in the alarm buffer.
3. The converter closes gaps in the alarm buffer that occurred when the removed alarms were
shifted in the alarm history by shifting the alarms that have not been removed "up".
4. The converter saves the received alarm as the latest alarm in the alarm buffer.
The alarm history saves up to 56 alarms.
In the alarm history, alarms are sorted according to the "alarm time received". The latest alarm
has Index [8].
Parameters
Table 9-4 Parameters of the alarm buffer and the alarm history
Parameter Description Factory setting
p2111 Alarm counter 0
r2122[0 … 63] Alarm code -
Warnings, faults and system messages
9.4 Alarms, alarm buffer, and alarm history
SINAMICS G120XA converter
748 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB