p2247[0...n] Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 7954
Min:
0.0 [s]
Max:
1000.0 [s]
Factory setting:
10.0 [s]
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: See also: p2248
Note
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2248[0...n] Technology controller motorized potentiometer ramp-down time / Tec_ctrMop t_rdown
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 7954
Min:
0.0 [s]
Max:
1000.0 [s]
Factory setting:
10.0 [s]
Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: See also: p2247
Note
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
r2250 CO: Technology controller motorized potentiometer setpoint after RFG / Tec_ctr mop aftRFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7954
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency: See also: r2245
p2251 Technology controller mode / Tec_ctrl mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0
Max:
0
Factory setting:
0
Description: Sets the mode for using the technology controller output.
Value: 0: Technology controller as main speed setpoint
Dependency: p2251 = 0 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
Parameters
7.3 Parameters
SINAMICS G120XA converter
610 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB