EasyManua.ls Logo

Siemens SINAMICS G120XA - BI: 2;3 Wire Control Command 2; 2;3 Wire CMD 2; BI: 2;3 Wire Control Command 3; 2;3 Wire CMD 3; BI: Limit Switch Start; Lim Switch Start; CO;BO: 2;3 Wire Control Control Word; 2;3 Wire STW

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dependency: See also: p0015, p3331, p3332, r3333
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3331[0...n] BI: 2/3 wire control command 2 / 2/3 wire cmd 2
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for command 2 for the two-wire control/three-wire control.
Dependency: See also: p0015, p3330, p3332, r3333
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3332[0...n] BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2273
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency: See also: p0015, p3330, p3331, r3333
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
r3333.0...3 CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
-
Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON inverted Yes No -
03 Reversing inverted Yes No -
Dependency: See also: p0015, p3330, p3331, p3332
p3340[0...n] BI: Limit switch start / Lim switch start
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the start of motion dependent on the sign of the setpoint.
Parameters
7.3 Parameters
SINAMICS G120XA converter
648 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents