Dependency: See also: p0015, p3331, p3332, r3333
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3331[0...n] BI: 2/3 wire control command 2 / 2/3 wire cmd 2
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for command 2 for the two-wire control/three-wire control.
Dependency: See also: p0015, p3330, p3332, r3333
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3332[0...n] BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2273
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency: See also: p0015, p3330, p3331, r3333
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
r3333.0...3 CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
-
Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON inverted Yes No -
03 Reversing inverted Yes No -
Dependency: See also: p0015, p3330, p3331, p3332
p3340[0...n] BI: Limit switch start / Lim switch start
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the start of motion dependent on the sign of the setpoint.
Parameters
7.3 Parameters
SINAMICS G120XA converter
648 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB