r4047 PM330 digital outputs status / PM330 DO status
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of the digital outputs of Power Module 330 (PM330).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X9.8: enable signal UDC link charged) High Low -
01 DO 1 (X9.11/X9.12: main contactor control) High Low -
Note
DO: Digital Output
p4095 PM330 digital inputs simulation mode / PM330 DI sim_mode
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Sets the simulation mode for digital inputs of the PM330 power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) Simulation Terminal eval -
01 DI 1 (X9.4, external fault) Simulation Terminal eval -
02 DI 2 (X9.5, Emergency Off category 0) Simulation Terminal eval -
03 DI 3 (X9.6, Emergency Off category 1) Simulation Terminal eval -
Dependency: The setpoint for the input signals is specified using p4096.
See also: p4096
Note
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
p4096 PM330 digital inputs simulation mode setpoint / PM330 DI sim setp
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2275
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Sets the setpoint for the input signals in the digital input simulation mode of the PM330 power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -
Dependency: The simulation of a digital input is selected using p4095.
See also: p4095
Note
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input