r0080[0...1] CO: Torque actual value / Actual torque
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dynamic index: -
Unit group: 7_1 Unit selection: p0505 Function diagram: 6714, 6799
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description: Display and connector output for actual torque value.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: See also: r0031, p0045
Note
The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
r0082[0...2] CO: Active power actual value / P_act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: r2004 Dynamic index: -
Unit group: 14_5 Unit selection: p0505 Function diagram: 6714, 6799
Min:
- [kW]
Max:
- [kW]
Factory setting:
- [kW]
Description: Displays the instantaneous active power.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency: See also: r0032
Note
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
r0087 CO: Actual power factor / Cos phi act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
p0096 Application class / Appl_class
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C2(1) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 6019
Min:
0
Max:
2
Factory setting:
0
Description: Setting the commissioning and control view for various application classes.
Value: 0: Expert
1: Standard Drive Control (SDC)
2: Dynamic Drive Control (DDC)
Parameters
7.3 Parameters
SINAMICS G120XA converter
374 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB