NOTICE
This parameter is pre-assigned in the case of motors from the motor list (p0301) if a bearing version (p0530) is
selected.
When selecting a catalog motor, this parameter cannot be changed (write protection). The information in p0530 should
be observed when removing write protection.
If p0532 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3).
p0573 Inhibit automatic reference value calculation / Inhibit calc
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Setting to inhibit the calculation of reference parameters (e.g. p2000) when automatically calculating the motor and
closed-loop control parameters (p0340, p3900).
Value: 0: No
1: Yes
NOTICE
The inhibit for the reference value calculation is canceled when new motor parameters (e.g. p0305) are entered and
only one drive data set exists (p0180 = 1). This is the case during initial commissioning.
Once the motor and control parameters have been calculated (p0340, p3900), the inhibit for the reference value
calculation is automatically re-activated.
Note
If value = 0:
The automatic calculation (p0340, p3900) overwrites the reference parameters.
If value = 1:
The automatic calculation (p0340, p3900) does not overwrite the reference parameters.
p0595 Technological unit selection / Tech unit select
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C2(5) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
1
Max:
48
Factory setting:
1
Description: Selects the units for the parameters of the technology controller.
For p0595 = 1, 2, the reference quantity set in p0596 is not active.
Value: 1: %
2: 1 referred no dimensions
3: bar
4: °C
5: Pa
6: ltr/s
7: m³/s
8: ltr/min
9: m³/min
10: ltr/h
11: m³/h
12: kg/s
Parameters
7.3 Parameters
SINAMICS G120XA converter
414 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB