Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Note
AO: Analog Output
r0774[0...2] CU analog outputs output voltage/current actual / CU AO U/I_outp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-
Max:
-
Factory setting:
-
Description: Displays the actual output voltage or output current at the analog outputs.
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Dependency: See also: p0776
Note
AO: Analog Output
p0775[0...2] CU analog outputs activate absolute value generation / CU AO absVal act
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
0
Max:
1
Factory setting:
0
Description: Activates the absolute value generation for the analog outputs.
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Note
AO: Analog Output
p0776[0...2] CU analog outputs type / CU AO type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
0
Max:
2
Factory setting:
0
Description: Sets the analog output type.
p0776[x] = 1 corresponds to a voltage output (p0774, p0778, p0780 are displayed in V).
p0776[x] = 0, 2 corresponds to a current output (p0774, p0778, p0780 are displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 437