4: Service
Note
A higher set access level also includes the lower one.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
p0010 Drive commissioning parameter filter / Drv comm. par_filt
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C2(1), T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2800, 2818
Min:
0
Max:
49
Factory setting:
1
Description: Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value: 0: Ready
1: Quick commissioning
2: Power unit commissioning
3: Motor commissioning
5: Technological application/units
15: Data sets
29: Only Siemens internal
30: Parameter reset
39: Only Siemens internal
49: Only Siemens internal
Dependency: See also: r3996
NOTICE
When the parameter is reset to a value of 0, short-term communication interruptions may occur.
Note
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have been
defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 = 15).
p0010 = 29, 39, 49: Only for internal Siemens use!
p0015 Macro drive unit / Macro drv unit
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: C1, C2(1) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
999999
Factory setting:
41
Description: Runs the corresponding macro files.
Dependency: See also: p1000, r8570
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 353