6.3.5 Cavitation protection
Overview
Cavitation problem can damage the impeller of the pumps, reduce the output water flow and
cause unexpected noise. The cavitation protection will generate a fault/warning when
cavitation conditions are deemed to be present. If the converter gets no feedback from the
pump transducer, it will trip to prevent cavitation damage. This function saves the maintenance
efforts and extends the lifetime expectancy of the system.
Function description
&DYLWDWLRQSURWHFWLRQHQDEOH
3,'6FDOHG
IHHGEDFN>@
6WDWXVZRUGELW3,'PLQLPXPOLPLWUHDFKHG
6WDWXVZRUGELW3,'PD[LPXP
OLPLWUHDFKHG
6WDWXVZRUGELW3,'LQYHUWHUUXQQLQJ
&DYLWDWLRQSURWHFWLRQGHOD\
3,'HQDEOHGLVDEOH
&DYLWDWLRQSURWHFWLRQWKUHVKROG
>@
7ULJJHUZDUQLQJ$
7ULJJHUIDXOW)
&DYLWDWLRQSURWHFWLRQGLVDEOHG
S
S
U
U
U
>V@
U
7
ุ
S
S
Parameters
Number Name Factory setting
p29625 Cavitation protection enable 0
p29626 Cavitation protection threshold 40%
p29627 Cavitation protection time 30 s
For more information about the parameters, see Chapter "Parameters (Page 349)".
Advanced commissioning
6.3 Pump control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 221