00 DI 0 (X133. 5) High Low -
01 DI 1 (X133. 6) High Low -
02 DI 2 (X133. 7) High Low -
03 DI 3 (X133. 8) High Low -
04 DI 4 (X133. 16) High Low -
05 DI 5 (X133. 17) High Low -
11 DI 11 (X131. 3, 4) AI 0 High Low -
12 DI 12 (X131. 10, 11) AI 1 High Low -
Dependency: See also: r0723
Note
AI: Analog Input
DI: Digital Input
r0723.0...12 CO/BO: CU digital inputs status inverted / CU DI status inv
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2119, 2120,
2121, 2130, 2131, 2132, 2133
Min:
-
Max:
-
Factory setting:
-
Description: Displays the inverted status of the digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X133. 5) High Low -
01 DI 1 (X133. 6) High Low -
02 DI 2 (X133. 7) High Low -
03 DI 3 (X133. 8) High Low -
04 DI 4 (X133. 16) High Low -
05 DI 5 (X133. 17) High Low -
11 DI 11 (X131. 3, 4) AI 0 High Low -
12 DI 12 (X131. 10, 11) AI 1 High Low -
Dependency: See also: r0722
Note
AI: Analog Input
DI: Digital Input
p0724 CU digital inputs debounce time / CU DI t_debounce
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.000 [ms]
Max:
20.000 [ms]
Factory setting:
4.000 [ms]
Description: Sets the debounce time for digital inputs.
Note
The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
Parameters
7.3 Parameters