NOTICE
When deactivating the I_max controller, the following must be carefully observed:
When the maximum current (r0067) is exceeded, the output current is no longer reduced. The drive is switched off
when the overcurrent limits are exceeded.
Note
The I_max limiting controller becomes ineffective if the ramp-function generator is deactivated with p1122 = 1.
p1341 = 0:
I_max frequency controller deactivated and I_max voltage controller activated over the complete speed range.
p1341[0...n] I_max frequency controller integral time / I_max_ctrl Tn
Access level: 3 Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6300, 6850
Min:
0.000 [s]
Max:
50.000 [s]
Factory setting:
0.300 [s]
Description: Sets the integral time for the I_max frequency controller.
Dependency: See also: p1340
Note
When p1341 = 0, the current limiting controller influencing the frequency is deactivated and only the current limiting
controller influencing the output voltage remains active (p1345, p1346).
In the case of power units with regenerative feedback (PM250, PM260), current limitation control for a regenerative
load is always implemented by influencing the frequency. This current limiting function is deactivated with p1340 =
p1341 = 0.
r1343 CO: I_max controller frequency output / I_max_ctrl f_outp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: 6300, 6850
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Displays the effective frequency limit.
Dependency: See also: p1340
r1344 I_max controller voltage output / I_max_ctrl U_outp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dynamic index: -
Unit group: 5_1 Unit selection: p0505 Function diagram: 6300
Min:
- [Vrms]
Max:
- [Vrms]
Factory setting:
- [Vrms]
Description: Displays the amount by which the converter output voltage is reduced.
Dependency: See also: p1340
p1345[0...n] I_max voltage controller proportional gain / I_max_U_ctrl Kp
Access level: 3 Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6300, 7017
Min:
0.000
Max:
100000.000
Factory setting:
0.000
Description: Sets the proportional gain for the I_max voltage controller.