p2140[0...n] Hysteresis speed 2 / n_hysteresis 2
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010
Min:
0.00 [rpm]
Max:
300.00 [rpm]
Factory setting:
90.00 [rpm]
Description: Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency: See also: p2155, r2197
p2141[0...n] Speed threshold 1 / n_thresh val 1
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
5.00 [rpm]
Description: Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency: See also: p2142, r2199
p2142[0...n] Hysteresis speed 1 / n_hysteresis 1
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010
Min:
0.00 [rpm]
Max:
300.00 [rpm]
Factory setting:
2.00 [rpm]
Description: Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO: r2199.1).
Dependency: See also: p2141, r2199
p2144[0...n] BI: Motor stall monitoring enable (negated) / Mot stall enab neg
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 8012
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the negated enable (0 = enable) of the motor stall monitoring.
Dependency: See also: p2163, p2164, p2166, r2197, r2198
See also: F07900
Note
When interconnecting the enable signal with r2197.7 then the stall signal is suppressed if there is no speed setpoint -
actual value deviation.
Parameters
7.3 Parameters
SINAMICS G120XA converter
588 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB