EMC-compliant setup of the machine or plant (Page 39)
Table 4-4 Maximum permissible motor cable length depending on EMC category
1)
Converter
frame size
Maximum motor cable length
Second
environ‐
ment
C3 Converters with
integrated filter
FSA … FSC 50 m
FSD … FSE 100 m
FSF … FSG 150 m
FSH … FSJ 100 m
Converters with‐
out line filters with
external C3 filter
FSA … FSF 50 m
1)
The values apply to a pulse frequency at the factory setting. If you set other pulse frequencies, you
must ensure that the EMC category is complied with on the plant or system side.
Without EMC category
Table 4-5 Maximum permissible motor cable length
1)
Converter frame
size
400 V
Maximum motor cable length
With shiel‐
ded motor
cable
Without output
reactor or dv/dt
filter
FSA … FSC 150 m
FSD … FSE 200 m
FSF … FSG 300 m
FSH … FSJ 150 m
2)
With 2 output
reactors in ser‐
ies
FSD … FSE 350 m
FSF … FSG 525 m
With 1 output
reactor
FSH … FSJ 300 m
2)
With un‐
shielded
motor cable
Without output
reactor or dv/dt
filter
FSA … FSC 300 m
FSD … FSE 300 m
FSF … FSG 450 m
FSH … FSJ 200 m
2)
With 2 output
reactors in ser‐
ies
FSD … FSE 525 m
FSF … FSG 800 m
With 1 output
reactor or dv/dt
filter
FSH … FSJ 450 m
2)
1)
The values are valid for a pulse frequency set at the factory
2)
The values are valid for a pulse frequency = 2 kHz
Wiring
4.1 Line supply and motor
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 65

Table of Contents