Figure 3-2 Grounding and high-frequency equipotential bonding measures in the control cabinet and
in the plant/system
Further information
Additional information about EMC-compliant installation is available in the Internet:
EMC installation guideline (http://support.automation.siemens.com/WW/view/en/
60612658)
3.1.2 Cables
Cables with a high level of interference and cables with a low level of interference are
connected to the converter:
Cables with a high level of interference:
Cable between the line filter and converter
Motor cable
Cable at the converter DC link connection
Cables with a low level of interference:
Cable between the line and line filter
Signal and data cables
Mounting
3.1 EMC-compliant setup of the machine or plant
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 41