6.9.2 Bypass
Overview
The "Bypass" function switches the motor between converter and line operation.
..
..
.
'212

'2&20
'212
'2&20
',
',
9287
*1'
.
.
.
U
%,S>@
U
%,S>@
S
U
S
U
Figure 6-84 Bypass control via converter
Requirements placed on the K1 converter contactor and K2 line contactor:
K1 and K2 are designed for switching under load.
K2 is designed for switching an inductive load.
K1 and K2 are interlocked against closing at the same time.
Requirements
The "Bypass" function is supported only for induction motors.
The "Flying restart" function must be activated for the "Bypass" function (p1200 = 1 or 4).
Flying restart – switching on while the motor is running (Page 318)
$
%
&
Advanced commissioning
6.9 Energy saving
SINAMICS G120XA converter
332 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB