Note
For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
r0720[0...4] CU number of inputs and outputs / CU I/O count
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2119
Min:
-
Max:
-
Factory setting:
-
Description: Displays the number of inputs and outputs.
Index: [0] = Number of digital inputs
[1] = Number of digital outputs
[2] = Number of digital input/outputs bidirectional
[3] = Number of analog inputs
[4] = Number of analog outputs
r0721 CU digital inputs terminal actual value / CU DI term act val
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2221,
2256
Min:
-
Max:
-
Factory setting:
-
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the simulation
mode (p0795.x = 1) to terminal mode (p0795.x = 0).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X133. 5) High Low -
01 DI 1 (X133. 6) High Low -
02 DI 2 (X133. 7) High Low -
03 DI 3 (X133. 8) High Low -
04 DI 4 (X133. 16) High Low -
05 DI 5 (X133. 17) High Low -
11 DI 11 (X131. 3, 4) AI 0 High Low -
12 DI 12 (X131. 10, 11) AI 1 High Low -
Note
AI: Analog Input
DI: Digital Input
r0722.0...12 CO/BO: CU digital inputs status / CU DI status
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2221,
2256
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of the digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
Parameters
7.3 Parameters
SINAMICS G120XA converter
426 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB