Note
AO: Analog Output
r0785.0...1 BO: CU analog outputs status word / CU AO ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of analog outputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 AO 0 negative Yes No -
01 AO 1 negative Yes No -
Note
AO: Analog Output
p0791[0...2] CO: Fieldbus analog outputs / Fieldbus AO
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-200.000 [%]
Max:
200.000 [%]
Factory setting:
0.000 [%]
Description: Setting and connector output to control the analog outputs via fieldbus.
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Dependency: See also: p0771
Note
AO: Analog Output
The following interconnections must be established to control the analog outputs via fieldbus:
- AO 0: p0771[0] with p0791[0]
- AO 1: p0771[1] with p0791[1]
p0795 CU digital inputs simulation mode / CU DI simulation
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2221,
2256
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description: Sets the simulation mode for digital inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X133. 5) Simulation Terminal eval -
01 DI 1 (X133. 6) Simulation Terminal eval -
02 DI 2 (X133. 7) Simulation Terminal eval -
03 DI 3 (X133. 8) Simulation Terminal eval -
04 DI 4 (X133. 16) Simulation Terminal eval -
05 DI 5 (X133. 17) Simulation Terminal eval -
11 DI 11 (X131. 3, 4) AI 0 Simulation Terminal eval -
Parameters
7.3 Parameters
SINAMICS G120XA converter
440 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB