Description: Determines the width of the dead zone at the analog input.
Analog input type unipolar (e.g. 0 ... +10 V):
The dead zone starts with the characteristic value x1/y1 (p0757/p0758).
Analog input type bipolar (e.g. -10 V ... +10 V):
The dead zone is located at the symmetrical center between characteristic value x1/y1 (p0757/p0758) and x2/y2
(p0759/p0760). The set value doubles the dead zone.
Index: [0] = AI0 (131 3/4)
[1] = AI1 (131 10/11)
[2] = Reserved
[3] = Reserved
Note
AI: Analog Input
p0771[0...2] CI: CU analog outputs signal source / CU AO S_src
Access level: 2 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2261
Min:
-
Max:
-
Factory setting:
[0] 21[0]
[1] 27[0]
[2] 0
Description: Sets the signal source for the analog outputs.
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Note
AO: Analog Output
r0772[0...2] CU analog outputs output value currently referred / CU AO outp act ref
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Displays the actual referred output value of the analog outputs.
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Note
AO: Analog Output
p0773[0...2] CU analog outputs smoothing time constant / CU AO T_smooth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
0.0 [ms]
Max:
1000.0 [ms]
Factory setting:
0.0 [ms]
Description: Sets the smoothing time constant of the 1st order lowpass filter for the analog outputs.
Parameters
7.3 Parameters
SINAMICS G120XA converter
436 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB