12 DI 12 (X131.10, 11) AI 1 Simulation Terminal eval -
Dependency: The setpoint for the input signals is specified using p0796.
See also: p0796
Note
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2221,
2256
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X133. 5) Simulation Terminal eval -
01 DI 1 (X133. 6) Simulation Terminal eval -
02 DI 2 (X133. 7) Simulation Terminal eval -
03 DI 3 (X133. 8) Simulation Terminal eval -
04 DI 4 (X133. 16) Simulation Terminal eval -
05 DI 5 (X133. 17) Simulation Terminal eval -
11 DI 11 (X131. 3, 4) AI 0 Simulation Terminal eval -
12 DI 12 (X131.10, 11) AI 1 Simulation Terminal eval -
Dependency: The simulation of a digital input is selected using p0795.
See also: p0795
Note
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
p0797[0...3] CU analog inputs simulation mode / CU AI sim_mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Sets the simulation mode for the analog inputs.
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved)
Dependency: The setpoint for the input voltage is specified via p0798.
See also: p0798
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 441