Note
CDS: Command Data Set
DDS: Drive Data Set
The following control bits are displayed in r0055:
Bit 00: r1198.0
Bit 01: r1198.1
Bit 02: r1198.2
Bit 03: r1198.3
Bit 04: r0837.0
Bit 05: r0837.1
Bit 08: r2349.0 (negated)
Bit 09: r1239.11
Bit 13: r2138.13 (negated)
Bit 15: r0836.1
r0056.0...15 CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2526
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word of the closed-loop control.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Initialization completed Yes No -
01 De-magnetizing completed Yes No -
02 Pulse enable available Yes No -
04 Magnetizing completed Yes No -
05 Voltage boost when starting Active Inactive 6301
06 Acceleration voltage Active Inactive 6301
07 Frequency negative Yes No -
08 Field weakening active Yes No -
09 Voltage limit active Yes No 6714
10 Slip limit active Yes No 6310
11 Frequency limit active Yes No -
12 Current limiting controller voltage output active Yes No -
13 Current/torque limiting Active Inactive 6060
14 Vdc_max controller active Yes No 6220,
6320
15 Vdc_min controller active Yes No 6220,
6320
r0060 CO: Speed setpoint before the setpoint filter / n_set before filt.
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: 2701, 6030,
6799, 6822
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Displays the actual speed setpoint at the input of the speed controller or U/f characteristic (after the interpolator).
Dependency: See also: r0020
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 369