EasyManua.ls Logo

Siemens SINAMICS G120XA - BI: Inhibit Master Control; Pcctrl Inhibit; BO: Master Control Active; Pcctrl Active

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dependency: See also: p0802, p0803
NOTICE
The memory card must not be removed while data is being transferred.
Note
If a parameter backup with setting 0 is detected on the memory card when the Control Unit is switched on
(PS000xxx.ACX), this is transferred automatically to the device memory.
When the memory card is inserted, a parameter backup with setting 0 (PS000xxx.ACX) is automatically written to the
memory card when the parameters are saved in a non-volatile memory (e.g. by means of "Copy RAM to ROM").
Once the data has been successfully transferred, this parameter is automatically reset to 0. If an error occurs, the
parameter is set to a value > 1000. Possible fault causes:
p0804 = 1001:
The parameter backup set in p0802 as the source on the memory card does not exist or there is not sufficient memory
space available on the memory card.
p0804 = 1002:
The parameter backup set in p0803 as the source in the device memory does not exist or there is not sufficient memory
space available in the device memory.
p0804 = 1003:
No memory card has been inserted.
p0806 BI: Inhibit master control / PcCtrl inhibit
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to block the master control.
Dependency: See also: r0807
Note
The commissioning software (drive control panel) uses the master control, for example.
r0807.0 BO: Master control active / PcCtrl active
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Bit field: Bit Signal name 1 signal 0 signal FP
00 Master control active Yes No 3030
Dependency: See also: p0806
NOTICE
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The commissioning software (drive control panel) uses the master control, for example.
Parameters
7.3 Parameters
SINAMICS G120XA converter
444 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents

Related product manuals