p0758[0...3] CU analog inputs characteristic value y1 / CU AI char y1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
-1000.00 [%]
Max:
1000.00 [%]
Factory setting:
0.00 [%]
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
The parameters for the characteristic do not have a limiting effect.
p0759[0...3] CU analog inputs characteristic value x2 / CU AI char x2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
-50.000
Max:
160.000
Factory setting:
[0] 10.000
[1] 10.000
[2] 20.000
[3] 100.000
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA, °C) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
The parameters for the characteristic do not have a limiting effect.
p0760[0...3] CU analog inputs characteristic value y2 / CU AI char y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
-1000.00 [%]
Max:
1000.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Parameters
7.3 Parameters
SINAMICS G120XA converter
434 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB