Routing cables outside the control cabinet
Maintain a minimum clearance of 25 cm between cables with a high level of interference and
cables with a low level of interference.
Using shielded cables for the following connections:
Converter motor cable
Signal and data cables
Connect the motor cable shield to the motor enclosure using a PG gland that establishes a
good electrical connection.
Requirements relating to shielded cables
Use cables with finely-stranded, braided shields.
Connect the shield to at least one end of the cable.
%DUHVKLHOG
0RXQWLQJSODWH
6KLHOGSODWH
&RQQHFWVKLHOG
7RRWKHG
WDSH
+RVHFODPS
Figure 3-4 Examples for EMC-compliant shield support
Attach the shield to the shield support directly after the cable enters the cabinet.
Do not interrupt the shield.
Only use metallic or metallized plug connectors for shielded data cables.
3.1.3 Electromechanical components
Surge voltage protection circuit
Connect surge voltage protection circuits to the following components:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Connect the surge voltage protection circuit directly at the coil.
Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors for
DC-operated coils.
Mounting
3.1 EMC-compliant setup of the machine or plant
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 43