Siemens SINAMICS G120XA - CO: VDC Controller Output (U;F); Vdc_Ctrl Output; Open-Loop;Closed-Loop Control Operating Mode; Op;Cl-Lp Ctrl_Mode; Vdc_Min Controller Speed Threshold (U;F); Vdc_Min N_Thresh

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Value: 0: Buffer Vdc until undervoltage, n<p1297 -> F07405
1: Buff. Vdc until undervolt., n<p1297 -> F07405, t>p1295 -> F07406
Note
For p1296 = 1:
The quick stop ramp entered in p1135 must not be equal to zero, to prevent overcurrent shutdown if F07406 is triggered.
p1297[0...n] Vdc_min controller speed threshold (U/f) / Vdc_min n_thresh
Access level: 3 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: -
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
50.00 [rpm]
Description: Sets the speed threshold for the Vdc-min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized .
Note
Exiting the Vdc_min control before reaching motor standstill prevents the regenerative braking current from increasing
significantly at low speeds, and after a pulse inhibit, means that the motor coasts down.
r1298 CO: Vdc controller output (U/f) / Vdc_ctrl output
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: 6320, 6854
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Displays the actual output of the Vdc controller (DC link voltage controller)
p1300[0...n] Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C2(1), T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6300, 6301,
6851, 8012
Min:
0
Max:
20
Factory setting:
0
Description: Sets the open and closed-loop control mode of a drive.
Value: 0: U/f control with linear characteristic
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
4: U/f control with linear characteristic and ECO
7: U/f control for a parabolic characteristic and ECO
20: Speed control (encoderless)
Dependency: For Standard Drive Control (p0096 = 1), settings p1300 = 0, 2 are possible, for Dynamic Drive Control (p0096 = 2) only
p1300 = 20 can be set.
Only operation with U/f characteristic is possible if the rated motor speed is not entered (p0311).
See also: p0300, p0311, p0500
NOTICE
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for the
ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 509