Procedure, FSD/FSE
1. Attach the shielding plate to the bottom of the converter and fasten it in place using four
screws .
2. If the converter has an integrated line filter, mount the EMC connecting bracket additionally.
a. Slide the EMC connecting bracket into the converter, so that it is held in the converter by
the clamping spring .
The EMC connecting bracket is positioned correctly if you feel some resistance when pulling
it out from the converter.
b. Having ensured that it is positioned correctly, fasten the EMC connecting bracket in place
using three screws .
1P
1P
You have now mounted the shield connection kit.
Procedure, FSF
1. Attach the shielding plate to the bottom of the converter and fasten it in place using four
screws .
2. If the converter has an integrated line filter, mount the EMC connecting bracket additionally
by fastening it to the shielding plate with four screws .
1P
1P
You have now mounted the shield connection kit.
Mounting
3.3 Mounting the converter
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 51