p2105[0...n] BI: 3rd acknowledge faults / 3rd acknowledge
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2546, 8060
Min:
-
Max:
-
Factory setting:
0
Description: Sets the third signal source to acknowledge faults.
Note
A fault acknowledgment is triggered with a 0/1 signal.
p2106[0...n] BI: External fault 1 / External fault 1
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for external fault 1.
Dependency: See also: F07860
Note
An external fault is triggered with a 1/0 signal.
p2107[0...n] BI: External fault 2 / External fault 2
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for external fault 2.
Dependency: See also: F07861
Note
An external fault is triggered with a 1/0 signal.
p2108[0...n] BI: External fault 3 / External fault 3
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: See also: p3110, p3111, p3112
See also: F07862
Note
An external fault is triggered with a 1/0 signal.
Parameters
7.3 Parameters
SINAMICS G120XA converter
578 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB