Dependency: The following applies: p2191< p2168 if p2168 <> 0
See also: p2181, p2182, p2184, p2193
See also: A07892, F07895, A07926
Note
For the setting p2191 = 0, the monitoring for dry running operation or belt breakage is deactivated.
Pre-assignment: p2191 = 5 % of the rated motor torque (p0333).
p2192[0...n] Load monitoring delay time / Load monit t_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8013
Min:
0.00 [s]
Max:
65.00 [s]
Factory setting:
10.00 [s]
Description: Sets the delay time to evaluate the load monitoring.
p2193[0...n] Load monitoring configuration / Load monit config
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8013
Min:
0
Max:
5
Factory setting:
1
Description: Sets the load monitoring configuration.
Value: 0: Monitoring switched out
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Monitoring load drop
4: Monitoring pump and load failure
5: Monitoring fan and load failure
Dependency: See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925, F07936
Note
p2193 = 4, 5 can only be combined with p2181 = 7, 8.
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2534
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the first status word of the monitoring functions.
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8022
01 |n_act| <= speed threshold value 2 p2155 Yes No 8010
02 |n_act| > speed threshold value 2 p2155 Yes No 8010
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8022
05 |n_act| <= n_standstill p1226 Yes No 8022
06 |n_act| > n_max Yes No 8010
Parameters
7.3 Parameters
SINAMICS G120XA converter
600 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB