p8991 USB memory access / USB mem acc
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
1
Max:
2
Factory setting:
1
Description: Selects the storage medium for access via the USB mass storage.
Value: 1: Memory card
2: Flash r/w internal
Note
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p9400 Safely remove memory card / Mem_card rem
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
100
Factory setting:
0
Description: Setting and display when memory card is "removed safely".
Procedure:
Setting p9400 = 2 results in a value of 3
--> The memory card can be removed safely. After removal the value sets itself to 0 automatically.
Setting p9400 = 2 results in a value of 100
--> The memory card cannot be removed safely. Removal may destroy the file system on the memory card. It may be
necessary to set p9400 = 2 again.
Value: 0: No memory card inserted
1: Memory card inserted
2: Request "safe removal" of the memory card
3: "Safe removal" possible
100: "Safe removal" not possible due to access
Dependency: See also: r9401
NOTICE
Removing the memory card without a request (p9400 = 2) and confirmation (p9400 = 3) may destroy the file system
on the memory card. The memory card will then no longer work properly and must be replaced.
Note
The status when the memory card is being "removed safely" is shown in r9401.
For value = 0, 1, 3, 100:
These values can only be displayed, not set.
r9401.0...3 CO/BO: Safely remove memory card status / Mem_card rem stat
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of the memory card.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Memory card inserted Yes No -
Parameters
7.3 Parameters
SINAMICS G120XA converter
682 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB