Note
When the "hibernation mode" function (p2398 = 1) is activated, its behavior is defined as to whether the technology
controller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0:
Hibernation mode operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Hibernation mode operates with technology controller (closed-loop)
r2399.0...8 CO/BO: Hibernation mode status words / Hib ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7038
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word of the "hibernation mode" function.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Hibernation mode enabled (p2398 <> 0) Yes No -
01 Hibernation mode active Yes No -
02 Hibernation mode delay active Yes No -
03 Hibernation boost active Yes No -
04 Hibernation mode motor switched off Yes No -
05 Hibernation mode switched off cyclic restart active Yes No -
06 Hibernation motor motor restarts Yes No -
07 Hibernation mode supplies total setpoint for ramp-fct
generator
Yes No -
08 Hibernation mode bypasses ramp-fct generator in setpoint
channel
Yes No -
Dependency: See also: p2398
See also: A07325
p2900[0...n] CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 1021
Min:
-10000.00 [%]
Max:
10000.00 [%]
Factory setting:
0.00 [%]
Description: Setting and connector output for a fixed percentage value.
Dependency: See also: p2901, r2902, p2930
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The value can be used to interconnect a scaling function (e.g. scaling the main setpoint).
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 635