Code numbers of the object types supported in BACnet
Object type Code number for BACnet
object type
Object type Code number for BACnet ob‐
ject type
Device Object 8 Analog Output Object 1
Binary Input Object 3 Analog Value Object 2
Binary Output Object 4 Multi-State Input Object 13
Binary Value Object 5 Octet String Values 47
Analog Input Object 0
Object properties of the "Device" object type
● Object_Identifier ● Application_Software_Version ● APDU_Timeout
● Object_Name ● Protocol_Version ● Number_Of_APDU_Retries
● Object_Type ● Protocol_Revision ● Max Master
● System_Status ● Protocol_Services_Supported ● Max Info Frames
● Vendor_Name ● Protocol_Object_Types_Supported ● Device Address Binding
● Vendor_Identifier ● Object_List ● Database Revision
● Model_Name ● Max_APDU_Length_Accepted
1)
● Firmware_Revision ● Segmentation_Supported
2)
1)
Length = 480,
2)
not supported
Object properties of other object types
Object
property
Object type
Binary In‐
put
Binary Out‐
put
Binary Val‐
ue
Analog In‐
put
Analog
Output
Analog
Value
Multi-State
Input
Octet
String Val‐
ues
Object_Identifier X X X X X X X X
Object_Name X X X X X X X X
Object_Type X X X X X X X X
Present_Value X X X X X X X X
Description X X X X X X X
Status_Flags X X X X X X X X
Event_State X X X X X X X
Out_Of_Service X X X X X X X
Units X X X
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
186 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB