4.2.5 Default setting of the interfaces
Overview
The function of most of the converter terminals can be set.
In order that you do not have to successively change terminal for terminal, several terminals
can be jointly set in the quick commissioning using default settings. Parameter p0015 in the
quick commissioning selects the appropriate default setting.
Table 4-7 Overview of default settings, Part 1/2
Default setting
Terminal 41 42 43 44 45 46
AI 0 Setpoint Setpoint Setpoint Setpoint Setpoint Setpoint local
AI 1 - PID actual value PID actual value PID actual value - Setpoint remote
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1 Current actual
value
Current actual
value
Current actual
value
Current actual
value
Current actual
value
Current actual
value
DI 0 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 local
DI 1 - - Service pump 1 Service pump 1 Fixed setpoint 1 ON/OFF2 re‐
mote
DI 2 - - Service pump 2 Service pump 2 Fixed setpoint 2 -
DI 3 - - - Service pump 3 Fixed setpoint 3 -
DI 4 - manual ↔ auto manual ↔ auto manual ↔ auto - local ↔ remote
DI 5 Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
DO 0 Fault Fault Fault Fault Fault Fault
DO 1 Operation Operation Operation Pump 1 Operation Operation
DO 2 Ready for opera‐
tion
Ready for opera‐
tion
Pump 1 Pump 2 Ready for opera‐
tion
Ready for opera‐
tion
DO 3 Alarm Alarm Pump 2 Pump 3 Alarm Alarm
Table 4-8 Overview of default settings, Part 2/2
Default setting
Terminal 47 48 49 51 52 54 55
AI 0 - - - - Setpoint local - Setpoint local
AI 1 PID actual
value
PID actual
value
PID actual
value
- - - -
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1 Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
DI 0 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 lo‐
cal
ON/OFF2 ON/OFF2 lo‐
cal
Wiring
4.2 Control interfaces
SINAMICS G120XA converter
82 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB