NOTICE
A maximum of 4 indices of the "trace" function can be used.
r2067[0...1] PZD maximum interconnected / PZDmaxIntercon
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Display for the maximum interconnected PZD in the receive/send direction
Index 0: receive (r2050, r2060)
Index 1: send (p2051, p2061)
p2080[0...15] BI: Binector-connector converter status word 1 / Bin/con ZSW1
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2472
Min:
-
Max:
-
Factory setting:
0
Description: Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form status word 1.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 567