EasyManua.ls Logo

Siemens SINAMICS G120XA - Technical Data of Inputs and Outputs

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
11
11.1 Technical data of inputs and outputs
Property Explanation
Fieldbus interface With RS485 interface for the following protocols:
USS
Modbus RTU
BACnet MS/TP
24 V power supply The converter generates its 24 V power supply from the line voltage.
Output voltages
24 V (max. 250 mA)
10 V (max. 10 mA)
Setpoint resolution 0.01 Hz
Digital inputs 6 (DI 0 … DI 5)
Electrically isolated only when supplied via an external isolated 24V supply
Type 3 in accordance with EN 61131-2
Voltage for "low" state: < 5 V
Voltage for "high" state: > 11 V
Current for 24 V input voltage: 4 mA
Minimum current for the "high" state: 2.5 mA
30 V maximum input voltage
PNP/NPN switchable
Compatible to SIMATIC outputs
10 ms response time for debounce time p0724 = 0
Analog inputs 2 (AI 0 ... AI 1)
Single-ended input
12-bit resolution
13 ms response time
Switchable between voltage and current via parameter setting:
-10/0 V ... 10 V: typical current drain: 0.1 mA, maximum voltage 35 V
0 mA ... 20 mA : maximum voltage 10 V, maximum current 80 mA
If AI 0 and AI 1 are configured as supplementary digital inputs: Voltage <
35 V, low < 1.6 V, high > 4.0 V, 13 ms ± 1 ms response time for debounce
time p0724 = 0.
Digital outputs 4 (DO 0 ... D0 3)
DO 0 ... DO 3: 250 V AC 1A/30 V DC 1A, for resistive, inductive or
capacitive load
1 type C relay, 3 type A relays
Update time: 2 ms
Max. 1 A (with ambient temperature ≤ 60 °C)
Overvoltage category: II
Switching cycle: 1 Hz
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 861