NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1058[0...n] Jog 1 speed setpoint / Jog 1 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3001, 3030
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
150.000 [rpm]
Description: Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: See also: p1055, p1056
p1059[0...n] Jog 2 speed setpoint / Jog 2 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3001, 3030
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
-150.000 [rpm]
Description: Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: See also: p1055, p1056
p1063[0...n] Setpoint channel speed limit / Setp_chan n_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3040
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
210000.000 [rpm]
Description: Sets the speed limit effective in the setpoint channel.
Dependency: See also: p1082, p1083, p1085, p1086, p1088
p1070[0...n] CI: Main setpoint / Main setpoint
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3001, 3030
Min:
-
Max:
-
Factory setting:
[0] 755[0]
[1] 0
[2] 0
[3] 0
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: See also: p1071, r1073, r1078
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 473