p2236[0...n] BI: Technology controller motorized potentiometer lower setpoint / Tec_ctrl mop lower
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7954
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology controller.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency: See also: p2235
p2237[0...n] Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: 7954
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description: Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency: See also: p2238
p2238[0...n] Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: 7954
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
-100.00 [%]
Description: Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency: See also: p2237
p2240[0...n] Technology controller motorized potentiometer starting value / Tec_ctrl mop start
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: 7954
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
0.00 [%]
Description: Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency: See also: p2230
r2245 CO: Technology controller mot. potentiometer setpoint before RFG / Tec_ctr mop befRFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7954
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency: See also: r2250
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 609