11.4 Technical data dependent on the power
Frame
size
Rated power
(kW)
Rated input
current (A)
Rated output
current (A)
Power loss (kW) Net weight (kg)
Based on Low Overload Without filter With filter Without filter With filter
FSA 0.75 2.1 2.2 0.043 0.043 3.1 3.4
1.1 2.8 3.1 0.055 0.055 3.1 3.4
1.5 3.6 4.1 0.071 0.072 3.1 3.4
2.2 5.3 5.6 0.085 0.086 3.1 3.4
3 6.6 7.3 0.116 0.117 3.1 3.4
FSB 4 8.5 8.8 0.118 0.119 5.9 6.2
5.5 11.5 12.5 0.172 0.175 5.9 6.2
7.5 15.8 16.5 0.225 0.231 5.9 6.2
FSC 11 25.8 25 0.306 0.31 7.2 7.7
15 28.5 31 0.387 0.402 7.2 7.7
FSD 18.5 41 37 0.54 0.54 16.2 17.9
22 46 43 0.63 0.64 16.2 17.9
30 56 58 0.92 0.93 16.2 17.9
37 73 68 0.97 0.98 18.4 19.1
45 84 82.5 1.26 1.27 16.6 18.3
FSE 55 106 103 1.56 1.57 27 27
FSF 75 143 136 1.72 1.74 60.3 66.8
90 164 164 2.16 2.18 60.3 66.8
110 200 201 2.27 2.29 64 68.3
132 234 237 2.86 2.89 64 68.3
FSG 160 278 289 -- 3.66 -- 105
200 348 364 -- 4.51 -- 113
250 417 436 -- 5.44 -- 120
FSH 315 617 590 -- 6.4 -- 132
355 684 645 -- 7.29 -- 134
400 760 725 -- 7.99 -- 137
FSJ 450 870 820 -- 9 -- 204
500 959 895 -- 10 -- 210
560 1060 1015 -- 11.2 -- 218
Technical data
11.4 Technical data dependent on the power
SINAMICS G120XA converter
866 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB