Instance
ID
Object name Description Possible values Text ac‐
tive
Text in‐
active
Ac‐
cess
type
Parameter
BV27 OFF2 OFF2 status RUN / STOP 0 1 C r0054.1
BV28 OFF3 OFF3 status
Note:
BV28 sets the r0054.4, r0054.5, and
r0054.6 bits
RUN / STOP 0 1 C r0054.2
BV50 ENABLE PID Enable technology controller ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C p2200
BV51 ENABLE
PID 0
Enable technology 0 controller ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C p11000
BV52 ENABLE
PID 1
Enable technology 1 controller ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C p11100
BV53 ENABLE
PID 2
Enable technology 2 controller ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C p11200
BV90 LOCAL
LOCK
Use MANUAL (operator panel) to
lock converter control
LOCK UN‐
LOCK
C p0806
BV93 CTL OVER‐
RIDE CMD
Converter control using BACnet
override control
ON/OFF 0 1 C r0054.10
Analog Input Objects
In‐
stance
ID
Object name Description Unit Range Access
type
Parameter
AI0 ANALOG IN 0 AI0 input signal V/mA converter-depend‐
ent
R r0752[0]
AI1 ANALOG IN 1 AI1 input signal V/mA converter-depend‐
ent
R r0752[1]
AI2 ANALOG IN 2 AI2 input signal V/mA converter-depend‐
ent
R r0752[2]
AI3 ANALOG IN 3 AI3 input signal V/mA converter-depend‐
ent
R r0752[3]
AI10 AI 0 SCALED Scaled AI 0 input signal % converter-depend‐
ent
R r0755[0]
AI11 AIN 1 SCALED Scaled AI 1 input signal % converter-depend‐
ent
R r0755[1]
AI12 AIN 2 SCALED Scaled AI 2 input signal % converter-depend‐
ent
R r0755[2]
AI13 AIN 3 SCALED Scaled AI 3 input signal % converter-depend‐
ent
R r0755[3]
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 189