Description: Displays the smoothed actual value of the DC link voltage.
Dependency: See also: r0070
NOTICE
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not supplied.
In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0026 sets itself to the lower value of the pulsating DC link voltage.
r0027 CO: Absolute actual current smoothed / Motor current
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dynamic index: -
Unit group: - Unit selection: - Function diagram: 5730, 6799,
8850, 8950
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description: Displays the smoothed absolute actual current value.
Dependency: See also: r0068
NOTICE
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the unsmoothed
value should be used.
Note
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
r0031 Actual torque smoothed / Actual torque
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dynamic index: -
Unit group: 7_1 Unit selection: p0505 Function diagram: 5730, 6799
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description: Displays the smoothed torque actual value.
Dependency: See also: r0080
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque actual value is available smoothed (r0031) and unsmoothed (r0080).
r0032 CO: Active power actual value smoothed / Power
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: r2004 Dynamic index: -
Unit group: 14_10 Unit selection: p0505 Function diagram: 5730, 6799,
8750, 8850, 8950
Min:
- [kW]
Max:
- [kW]
Factory setting:
- [kW]
Parameters
7.3 Parameters
SINAMICS G120XA converter
356 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB