Description: Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p15 and p1500 are
re-established and all of the dependent motor, open-loop and control-loop control parameters are calculated
(corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p15 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value: 0: No quick parameterization
1: Quick parameterization after parameter reset
2: Quick parameterization (only) for BICO and motor parameters
3: Quick parameterization for motor parameters (only)
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associated
with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motor: p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628
synchronous motor: p0326, p0327, p0352, p0604, p0605
r3925[0...n] Identification final display / Ident final_disp
Access level: 3 Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the commissioning steps that have been carried out.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor/control parameters calculated (p0340 = 1, p3900 > 0) Yes No -
02 Motor data identification carried out at standstill (p1910 = 1) Yes No -
03 Rotating measurement carried out (p1960 = 1, 2) Yes No -
08 Identified motor data are automatically backed up Yes No -
11 Automatic parameterization as Standard Drive Control Yes No -
12 Automatic parameterization as Dynamic Drive Control Yes No -
14 First motor commissioning Yes No -
15 Equivalent circuit diagram parameters changed Yes No -
18 Circle identification executed Yes No -
Note
The individual bits are only set if the appropriate action has been initiated and successfully completed.
The identification final display is reset when changing the type plate parameters.
Parameters
7.3 Parameters
SINAMICS G120XA converter
656 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB