EasyManua.ls Logo

Siemens SINAMICS G120XA - CO: Free Tec_Ctrl 1 Actual Value after Limiter; Ftec1 Act V Af Lim; CO: Free Tec_Ctrl 1 System Deviation; Ftec1 Sys Dev; Free Tec_Ctrl 1 Actual Value Inversion; Ftec1 Act V Inv; Free Tec_Ctrl 1 Differentiation Time Constant; Ftec1 D Comp T

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
p11171 Free tec_ctrl 1 actual value inversion / Ftec1 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0
Max:
1
Factory setting:
0
Description: Sets the inversion of the actual value signal of the free technology controller 1.
Value: 0: No inversion
1: Inversion
r11172 CO: Free tec_ctrl 1 actual value after limiter / Ftec1 act v af lim
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_3 Unit selection: p11126 Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the actual value after the limiter of the free technology controller 1.
r11173 CO: Free tec_ctrl 1 system deviation / Ftec1 sys dev
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_3 Unit selection: p11126 Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the system deviation of the free technology controller 1.
p11174 Free tec_ctrl 1 differentiation time constant / Ftec1 D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
0.000 [s]
Description: Sets the time constant for the differentiation (D component) of the free technology controller 1.
Note
Value = 0: Differentiation is deactivated.
p11180 Free tec_ctrl 1 proportional gain / Ftec1 Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.000
Max:
1000.000
Factory setting:
1.000
Description: Sets the proportional gain (P component) of the free technology controller 1.
Note
Value = 0: The proportional gain is deactivated.
Parameters
7.3 Parameters
SINAMICS G120XA converter
696 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents

Related product manuals