Parameters
The parameters differ depending on the motor control mode.
Table 6-69 Parameters for U/f control
Number Name Factory setting
p0210 Device supply voltage 400 V
p1280[D] Vdc controller configuration (U/f) 1
r1282 Vdc_max controller, switch-on level (U/f) - V
p1283[D] Vdc_max controller, dynamic factor (U/f) 100%
p1284[D] Vdc_max controller, time threshold (U/f) 4 s
p1290[D] Vdc controller proportional gain (U/f) 1
p1291[D] Vdc controller integral time (U/f) 40 ms
p1292[D] Vdc controller derivative-action time (U/f) 10 ms
p1294 Vdc_max controller ON level for automatic detection (U/f) 0
Table 6-70 Parameters for vector control
Number Name Factory setting
p0210 Device supply voltage 400 V
p1240[D] Vdc controller configuration (vector control) 1
r1242 Vdc_max controller, switch-on level - V
p1243[D] Vdc_max controller, dynamic factor 100%
p1250[D] Vdc controller proportional gain 1
p1251[D] Vdc controller integral time 0 ms
p1252[D] Vdc controller derivative-action time 0 ms
p1254 Vdc_max controller ON level for automatic detection 0
Further information is provided in the parameter list.
6.7.6 Monitoring the driven load
In many applications, the speed and the torque of the motor can be used to determine whether
the driven load is in an impermissible operating state. The use of an appropriate monitoring
function in the converter prevents failures and damage to the machine or plant.
Examples:
● For fans, an excessively low torque indicates a torn drive belt.
● For pumps, insufficient torque can indicate a leakage or dry-running.
● The motor can be blocked by an excessively high torque at a low speed.