p29596[0...n] Deragging forward time / Derag fw time
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [s]
Max:
1000.00 [s]
Factory setting:
5.00 [s]
Description: Defines the duration time at each forward speed for deragging.
p29597[0...n] Deragging reverse time / Derag rev tim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [s]
Max:
1000.00 [s]
Factory setting:
5.00 [s]
Description: Defines the duration time at reverse speed for deragging.
p29598[0...n] Number of deragging cycles / Derag cycs
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
1
Max:
999
Factory setting:
1
Description: The number of the deragging cycle is repeated
p29610[0...n] Pipe filling enable / PF En
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Enable the pipe filling function.
Value: 0: The pipe filling function is disabled
1: The pipe filling function is enabled
Note
The pipe filling function allows the inverter to fill an empty pipe slowly when the inverter works for the first time after each
power-up.
p29611[0...n] Pipe filling mode / PF mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Selects the mode for pipe filling.
Value: 0: The pipe is filled based on specified time
1: The pipe is filled based on the actual pressure feedback
Parameters
7.3 Parameters