r11094 CO: Free tec_ctrl 0 output signal / Ftec0 out_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the output signal of the free technology controller 0.
p11097 CI: Free tec_ctrl 0 limit maximum signal source / Ftec0 lim max s_s
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-
Max:
-
Factory setting:
11091[0]
Description: Sets the signal source for the maximum limit of the free technology controller 0.
Dependency: See also: p11091
p11098 CI: Free tec_ctrl 0 limit minimum signal source / Ftec0 lim min s_s
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-
Max:
-
Factory setting:
11092[0]
Description: Sets the signal source for the minimum limit of the free technology controller 0.
Dependency: See also: p11092
p11099 CI: Free tec_ctrl 0 limit offset signal source / Ftec0 lim offs
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the limit offset of the free technology controller 0.
p11100 BI: Free tec_ctrl 1 enable / Ftec1 enab
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to switch in/switch out the free technology controller 1.
1 signal: The technology controller is switched in.
0 signal: The technology controller is switched out.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 691