Number Name Factory setting
p29594 Ramp-up time 5 s
p29595 Ramp-down time 5 s
p29596 Deragging forward time 5 s
p29597 Deragging reverse time 5 s
p29598 Deragging cycle 1
Note: Before enabling the deragging via p29590, make sure the converter is in OFF status.
For more information about the parameters, see Chapter "Parameters (Page 349)".
Interaction with other functions
● Deragging signal is ignored if the converter is restarted under the command of essential
service mode, bypass operation, automatic restart, hibernation mode or multi-pump
switching-in.
● Deragging is interrupted if essential service mode, bypass, or hibernation mode is activated.
Advanced commissioning
6.3 Pump control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 223