4.1.4.5 Connecting the cable shields (FSA ... FSG only)
For EMC-compliant wiring, you must connect the cable shields to the shield plate of the
converter.
Use shielded cables for the following connection:
● Communication cable
● Control cable
● Motor cable
Before connecting the cable shields, you need to strip the cable insulation.
Connecting the cable shields, FSA ... FSC
The shield support for converter FSB is displayed as
an example.
① Unshielded line cable
② Cable tie
③ Shielded communication cable
④ Unlacquered, good electrically conducting
mounting plate
⑤ Shielded control cable
⑥ Toothed tape
⑦ Shielded motor cable
Note
For FSA … FSC, connect the cable shields of the communication cable and the control cable
to the same point of the shield plate using one toothed tape.
Wiring
4.1 Line supply and motor
SINAMICS G120XA converter
74 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB