p1014[0...n] CO: Fixed speed setpoint 14 / n_set_fixed 14
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Setting and connector output for fixed speed setpoint 14.
Dependency: See also: p1020, p1021, p1022, p1023, r1024
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1015[0...n] CO: Fixed speed setpoint 15 / n_set_fixed 15
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Setting and connector output for fixed speed setpoint 15.
Dependency: See also: p1020, p1021, p1022, p1023, r1024
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1016 Fixed speed setpoint select mode / n_set_fix select
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 3010, 3011
Min:
1
Max:
2
Factory setting:
1
Description: Sets the mode to select the fixed speed setpoint.
Value: 1: Direct
2: Binary
Note
For p1016 = 1:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1004.
Up to 16 different setpoints are obtained by adding the individual fixed speed setpoints.
For p1016 = 2:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1015.
p1020[0...n] BI: Fixed speed setpoint selection Bit 0 / n_set_fixed Bit 0
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3010,
3011
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for selecting the fixed speed setpoint.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 465